GPFC250 Commercial/GPFM250 Medical
250 Watt Global Performance Switchers
GLOBAL PERFORMANCE SWITCHERS
FEATURES:
? 3.6 watts/cu.in. power density
? Compact size (5.0” x 8.0” x 1.75”)
? Power factor corrected to IEC 1000-3-2, Class A
? Less than 300 μA leakage
? Conducted EMI exceeds FCC Class B and CISPR 22 Class B
(Commercial models) and CISPR 11 Class B (Medical models)
? Commercial Approved to UL1950, IEC950, EN60950 and
CSA 22.2 No. 950
? Medical Approved to UL2601-1, IEC601-1/60601-1 and
CSA-C22.2 No. 601.1
? 2-year warranty
? RoHS Compliant Model Available (G suffix)
SPECIFICATIONS
Ac Input
85-264 Vac, 47-63 Hz single phase.
EMI/EMC Compliance
All models include built-in EMI filtering to meet emissions requirements:
Input Current
Maximum input current 3.7 A at 90 Vac, 60 Hz with full rated load. Input cur-
rent harmonic content meets the requirements of IEC1000-3-2 Class A for all
load conditions.
Hold-upTime
25 ms minimum from loss of ac input at full load, nominal line (115 Vac).
Minimum Load: No minimum load required
EMI SPECIFICATIONS
Conducted Emissions GPFC250
Conducted Emissions GPFM250
Static Discharge
RF Field Susceptibility
Fast Transients/Bursts
Surge Susceptibility
COMPLIANCE LEVEL
EN55022 Class B; FCC Class B
EN55011 Class B: FCC Class B
EN61000-4-2, 6 kV contact, 8 kV air
EN61000-4-3, 3 V/meter
EN61000-4-4, 2 kV, 5 kHz
EN61000-4-5, 1 kV diff., 2 kV com.
Output Power
250 W fan cooled, 180 W convection. See chart for models under 12 V.
Overload Protection
Fully protected against short circuit and output overload. Short circuit protec-
tion is cycling type power limit or foldback type depending on model and
output. Recovery after fault is automatic. Individual output current limits are
a function of load distribution and degree of overload.
Output Noise
0.5% rms, 1% pk-pk, 20 MHz Bandwidth, differential mode. Measured with
noise probe directly across output terminals of the power supply.
Transient Response
Main Output–500 μs typical response time for return to within 0.5% of final
value for a 50% load step change, Di/Dt< 0.2 A/μs. Maximum voltage devia-
tion is 3.5%.
Remote Sense
Provided as a standard feature. Capable of compensating for 0.25 V total of
cabling losses in voltage.
Overvoltage Protection
Built in on all models. Output voltage decay is dependent upon loading.
Voltage Adjustment
Main output ±5%.
Efficency
Minimum 80% on 12-48 V units, 75% on 5 & 3.3 V units at full rated load.
Input Protection
Internal ac fuses provided on all models. Fuses do not blow on overload or
short circuit—fuses blow only if catastrophic failure occurs in the unit.
Inrush Current
Inrush 240 Vac is less than 37 A, averaged over the first ac half-cycle under cold
start conditions. Limiting provided by internal thermistors.
Fan Output
An additional 12 Vdc, 250 mA output suitable for powering a dc fan is included in
all models.
Thermal Shutdown
Provided as a standard feature. Designed to protect unit from prolonged over
temperature.
Power Fail
TTL or CMOS compatible output goes low (<0.5 V) 8 ms before output voltage
drops more than 4% below nominal voltage upon loss of ac power. The signal is
factory set to trip when input power can no longer sustain the output.
Temperature Coefficient
0.03% / °C typical on all outputs.
Leakage Current
70μA under normal conditions (132 Vac @ 60 Hz).
Maximum under single fault conditions (264 Vac @ 60Hz), 250 μA.
Power Good
TTL/CMOS compatible output goes high more than 100 ms after V1 reaches the
under voltage threshold and should assure that sufficient energy is stored in the
input
section to provide normal power fail/shutdown. The signal will fall to a low state
(<0.5 V) when V1 goes below 95% of the rated voltage.
External Off
TTL/CMOS compatible input shuts down power converter. A logic high (>2.7 V
with 400 uA source) shuts down the power converter. A logic low (<0.5 V) or an
open circuit allows the supply to run. 3.3 V & 5 V models require 25 mA source.
All specifications are typical at nominal input, full load at 25 O C unless otherwise stated
相关PDF资料
GPM130E PS MEDICAL QUAD OUT +5,15,24,-15
GPM140-28 POWER SUP SWITCHER 140W 28V MED
GPM200D PWR SUP SWITCHER 200W QUAD MED
GPM225-28 POWER SUP SWITCHER 225W 28V MED
GPM40B PWR SPLY MEDICAL TRI OUT 5-+15
GPM55E PS MEDICAL QUAD OUT +5,15,24,-15
GPM80-12G PWR SUPPLY MED SWITCH 12V 6.7A
GPMP600-28 POWER SUPPLY 28V 600 WATT MED
相关代理商/技术参数
GPFM250-28G 功能描述:线性和开关式电源 250W 28V @ 6.5A RoHS:否 制造商:TDK-Lambda 产品:Switching Supplies 开放式框架/封闭式:Enclosed 输出功率额定值:800 W 输入电压:85 VAC to 265 VAC 输出端数量:1 输出电压(通道 1):20 V 输出电流(通道 1):40 A 商用/医用: 输出电压(通道 2): 输出电流(通道 2): 安装风格:Rack 长度: 宽度: 高度:
GPFM250-3.3 功能描述:线性和开关式电源 250W 3.3V @ 36A RoHS:否 制造商:TDK-Lambda 产品:Switching Supplies 开放式框架/封闭式:Enclosed 输出功率额定值:800 W 输入电压:85 VAC to 265 VAC 输出端数量:1 输出电压(通道 1):20 V 输出电流(通道 1):40 A 商用/医用: 输出电压(通道 2): 输出电流(通道 2): 安装风格:Rack 长度: 宽度: 高度:
GPFM250-31 制造商:SL Power Electronics 功能描述:PN may be NE DW 制造商:SL Power Electronics 功能描述:- Bulk
GPFM250-31G 制造商:SL Power Electronics 功能描述:SWITCHER, HAZMAT - Bulk
GPFM250-48 功能描述:线性和开关式电源 250W 48V @ 3.8A RoHS:否 制造商:TDK-Lambda 产品:Switching Supplies 开放式框架/封闭式:Enclosed 输出功率额定值:800 W 输入电压:85 VAC to 265 VAC 输出端数量:1 输出电压(通道 1):20 V 输出电流(通道 1):40 A 商用/医用: 输出电压(通道 2): 输出电流(通道 2): 安装风格:Rack 长度: 宽度: 高度:
GPFM250-48-107 制造商:SL Power Electronics 功能描述:PT/PT3487546
GPFM250-48-108G 制造商:SL Power Electronics 功能描述:SWITCHER, HAZMAT - Bulk
GPFM250-48C 制造商:SL Power Electronics 功能描述:SWITCHER - Bulk